TLAR-S Current Clamp

20/200A AC current probe. Safely measure electrical current for power quality investigations. 600VAC, CAT III rated, the smaller clamp fits easily into small tight enclosures. Available in 2, 3 and 4 probe configurations.

  • CAT III 600V rating
  • Switchable 20A and 200A AC full scale ranges
  • 5 x 1.67 x 0.93 in [128 x 42.5 x 23.5 mm]
  • 4ft Probe leads

Description

Electrical Specifications

Current Ranges: 20A, 200A AC
Operating Limit: 200A Continuous
Frequency Range: 40 to 10kHz
Working Voltage: 600 VAC max
Influence of conductor position in jaw: 0.5% of reading at 50/60Hz
Influence of adjacent conductor: 1.50%
Influence of frequency: 40Hz to 1kHz: 3% of reading, 1kHz to 10kHz: 12% of reading

Phase Shift

1-20A: ≤3 degrees
20-80A: ≤2 degrees
80-200A: ≤2.5 degrees

Accuracy

20A scale: 1 to 20 A: 1.5% of reading ±0.1A
200A scale: 1.5% of reading ±0.5A

Safety

Rating: UL 61010B-1, IEC 61010-1, 600V CAT III

PMI Recorder Capability

10A range only with iVS-3/600E and ViPs with SNs lower than 61000, otherwise adjustable 20A/200A range

Environmental

Operating Temp: 14 to 131°F -10 to 55°C
Operating Relative Humidity: 10-35°C 85% RH
Case Protection: Probes – IP40, Enclosure – IP65

Physical Dimensions

Maximum Conductor Size: 5 x 1.67 x 0.93 in bus bar 15 x 17 mm
Probes: 5.47 x 2.00 x 1.18 in (139 x 51 x 30 mm)
Enclosure: 2.36 x 1.38 x 0.67 in
Weight: TLAR+200/3 – 0.75 lb TLAR+200/4 – 1.00 lb
Probe Leads: 4 ft, 600V rating
Output Cable: 9 in, 600V rating