Description
Inputs
AC Voltage:
80 to 140 V RMS
0 to 75 V RMS neutral-ground
AC Current: 0 to 70 A (15 amps continuous)
Sample Rate: 256 samples/cycle
Channels
Voltage: 2 channels
Current: 1 channel
Basic Measurements
RMS Voltage: Volts
RMS Current: Amps
Real Power: Watts
Apparent Power: VAs
Reactive Power: VARs
Power Usage: kWh, kVARh, kVAh
Advanced Power
Phase Angle: Degrees
Power Fact: Watts/VA
Displacement PF: cos (phase angle)
Accuracy
Voltage: 0.50% of full scale
Current: 1.0% of full scale
Power: 1.0% of full scale
Phase Angle: 1.0°
Power Factor: ±0.02
Displacement PF: ±0.02
Power Fail Operation
The recorder can operate without any input voltage for up to 1 minute.
Harmonics
Voltage: to the 51st
Current: to the 51st
Measures: Magnitude, phase, THD
Safety
150 V CAT II, UL Listed, UL 60730-1/CSA E60730-1, Indoor use only, Max load 1875VA
Communications
Cell Modem or WiFi
Information Storage
Data Storage: 64 MB in device, unlimited with PQ Canvass cloud storage
Record Settings
Interval Graphs: 1 cycle to 4 hour interval, user selected, stop-when-full or wrap-around memory modes
Significant Change: 1V to 8V in 1 V steps
Flicker Settings: User-defined, or conform to IEEE 1453/IEC 61000-4-15, and IEEE Std. 141
Waveform Capture: Voltage and current threshold, periodic capture, waveshape, event cross triggers
CBEMA/ITIC: Triggered event capture
Power Supply Requirements
Voltage: 70-140VAC Line to Neutral (47-63 Hz)
Power Consumption: 4 Watts max
Environmental
Temperature: 5°C to 60°C
Pressure: 500 – 1100 hPa
Humidity: 10 – 95% RH
Physical Dimensions
Size: 4.9” L x 2.7” W x 1.25” H
Weight: 0.5 lbs