Description
Inputs
AC Voltage: 0 to 600 VACcontinuous
AC Current: 200 Amps RMS (Forms 12S, 14S, 15S, 16S, 17S) 25 Amps (Forms 6S, 8S, 9S)
Sample Rate: 128 samples/cycle/channel
Channels
Voltage: 2 or 3 channels, depending on form
Current: 2 or 3 channels, depending on form
Measured Quantities Per Cycle
RMS Voltage: Volts
RMS Current: Amps
Real Power: Watts
Apparent Power: VAs
Reactive Power: VARS
Phase Angle: Degrees
Power Factor: Watts/VA
Displacement PF: cos (phase angle)
Power Usage: kWh, kVARh, kVAh
Accuracy
Voltage: 0.33% of full scale
Current: 1.0% of full scale
Power: 1.0% of full scale
Phase Angle: 1.0°
Power Factor: ±0.02
Displacement PF: ±0.02
Harmonics
Voltage: to the 31st
Current: to the 31st
Measures: magnitude, THD
Communications
Type: RS232 port
Remote: n/a
Data Rate: 4,800 to 38,000 baud
Information Storage
Interval Graphs: 2.1 MB
Significant Change: 1000 records
Flicker: 1000 records
Waveform Capture: 384 KB
Record Settings
Interval Graphs: User selected, stop-when-full, or wrap around memory modes Significant Change
Significant Change: 1V to 8V in 1V steps
Flicker Settings: User-defined, or conform to IEEE Std. 141
Waveform Capture: Voltage and current threshold
Power Supply
Power Consumption: Less than 2.5 watts
Operating Temp: -20°F to +135°F
Shock: 60 Hz to 2kHz, Acceleration 25G
Physical Dimension
Vibration: 10 Hz to 60 Hz, Amplitude 1.8 mm
Size: 4.625” x 6.75”
Weight: 3.6 lbs
Power Fail Operation
Can operate without any input voltage for up to 30 minutes. This allows it to record down to 0 volts on all channels during power outages.