Description
Inputs
AC Voltage: 0 to 600 V RMS continuous per phase
AC Current: 0 to 5000 A RMS
Sample Rate: 15,360 samples per second/channel; 256 samples per cycle
Channels
Voltage: 3 channels
Current: 3 channels
Measured Quantities Per Cycle
RMS Voltage: Volts
RMS Current: Amps
Real Power: Watts
Apparent Power: VAs
Reactive Power: VARs
Phase Angle: Degrees
Power Factor: Watts/VA
Displacement PF: cos (phase angle)
Power Usage: kWh, kVARh, kVAh
Accuracy
Voltage: ±0.33% of full scale
Current: ±1.0% of full scale w/o probe
Power: ±1.0% of full scale w/o probe
Phase Angle: ±1.0° w/o probe
Power Factor: ±0.02 w/o probe
Displacement PF: ±0.02 w/o probe
Safety
Designed to IEC 61010-1, 600 V CAT III
Harmonics
Voltage: to the 51st
Current: to the 51st
Measures: magnitude, phase, THD
Communications
Wi-Fi, Bluetooth, USB
Information Storage
Data Storage: 128 MB onboard storage, unlimited cloud storage
Record Settings
Interval Graphs: 1 cycle to 4 hour interval. User selected, stop-when-full, or wrap around memory modes
Significant Change: 1V to 8V in 1V steps
Flicker: User-defined, or conform to IEEE 1453/IEC 61000-4-15, and IEEE Std. 141
Waveform Capture: Voltage and current threshold, periodic capture, waveshape, event cross triggers
Power Supply Requirements:
Voltage: 60-600VAC Channel 1 to Common (47-63Hz)
Power Consumption:3 Watts max, 5 VA max at 600 V
Operating Temp: -20°F to +135°F
Humidity: Less than or equal to 85%
Shock: 60 Hz to 2 kHz, acceleration 25G
Vibration: 10 Hz to 60 Hz, amplitude 1.8mm
Max Altitude: 2.0 km (6560 ft), derated above 2.0 km
Physical Dimensions
Size: 1.78″ x 4.79″
Weight: less than 1 lb
Case: NEMA 4X
Power Fail Operations
5 minutes with super capacitor ride through for recording



Contact Sales